Body thermal: the J501's cooler in the closed body (B7, D61)

The P3 shell closes the body round the J501 and its G48R cooler. This page is the hand model the plan asks for first: where the cooler's 9215 fan works once the body is closed, what the body's inlet and outlet add to its load, the louvres that let the air in, and the temperatures at 40 W.

The fan blows up (the j501-agx project, commit 94da39d, from the user's look at the fitted cooler; this page was first written for a fan blowing down and was turned round the same day). It draws air in through the fin block's open ±y sides and blows it out of its top. In the body: the room's air comes in through the side walls' louvres, crosses the body past the power supplies, goes through the fins and the fan, up the fan duct, through the deck's cells and the turret plate's opening, and out of the riser's open sides under the turret. The losses are the same openings either way; what changes is the temperatures: the cooler now breathes the body's air, warmed by everything else in it. Numbers: cad/body_thermal.py → exports/body/thermal/hand_model.json (regenerate, never edit). Every input says where it comes from: the J501 project's parameters (vendored in references/vendor/j501/, B10), this body's CAD, Idel'chik's Handbook of Hydraulic Resistance for the loss coefficients, or "assumed". Written 2026-10-27.

The acceptance is a thermometer on the robot (B16, D61): the cooler's inlet (at the fins' sides) within 3 K of the room, the module's plate <= 70 °C, the exhaust <= 45 °C where it leaves the riser, at 40 W. The CFD (the j501-agx project's tools/thermal.py on cadagent.cfd) runs only once the J501's own Rev 0.9-g48r case reports itself calibrated and steady; today its exports/simulation-checks.json says the fins are not calibrated and the plate's margin is unknown, so no CFD was run here (one heavy solver at a time; the shared machines are loaded).

1. The model

Value Source
Fan 9215-Y at full speed: 28.1 Pa at no flow, 93.9 m³/h free air, a straight line between J501 thermal.fan (S06)
Cooler's own resistance 19.9 Pa at 27.5 m³/h (16.2 CFM), as k Q² the J501 box's CFD operating point at ce018d5 (run with the fan blowing down; all of it given to the cooler: conservative)
Deck outlet (P1 deck as cut) 31 cells, 8 mm square on an 11 mm pitch: 1,924 mm², open ratio 0.51, ζ = 1.39 on the cells' velocity CAD (body_frame.intake_cells, round the fan at robot (-60, 9)); Idel'chik thin perforated plate
Riser's open sides (out) 4 x 62 x 21 mm = 5,208 mm², ζ 1.5 (a 90° turn and out) CAD; ζ assumed
Inlet louvres 14 slots 4 x 46 mm a side (2,528 mm²), ζ 2.0 CAD (body_shell.LOUVRE); Idel'chik grilles (1.6-2.4)
Heat into the body 57.7 W: the module 40, the carrier 5, the TRACO TEP 150-4812WI 8.7 (70 W out at 89 %), the VESCs and boards 4 J501 power modes; TRACO efficiency; the rest assumed
Plate 0.6 K/W heatsink + 0.15 K/W pad and spreader assumed (Seeed publishes no G48R curve)

The room's air comes in through the louvres in the side walls' rear halves (beside the cooler's fins, above the J501's port hatch), into the fins at ±y; the fan blows it up a printed duct from 2 mm over the fan frame to the turret plate's opening (body_shell.fan_duct), out through the deck's cells and the riser's sides. The duct keeps the exhaust from spilling into the body and coming back round through the fins (the J501 box re-breathed its exhaust: +3.5 K without its skirt). The exhaust leaves 20-40 mm above the deck, sideways under the turret; the louvres are below the deck's lip, 20-70 mm lower, and warm air rises, so it should not come back in (B16 checks the inlet).

2. Results

Case Flow The body adds Deck outlet Louvre inlet Cooler's inlet over the room Through the cooler Out of the riser
P1 deck as cut, P3 louvres 12.9 CFM (21.9 m³/h) 9.0 Pa 7.3 Pa 1.7 Pa 2.5 K 5.6 K 33.1 °C
Rev B deck, cells on the minimum web over the fan's circle 13.2 CFM 8.3 Pa 6.5 Pa 1.8 Pa 2.4 K 5.5 K 32.9 °C
Rev B deck with a plenum to r 60 (57 cells) 14.3 CFM 5.5 Pa 3.4 Pa 2.1 Pa 2.2 K 5.1 K 32.3 °C

3. Open